RelayHelper Spectrogram

RelayHelper Spectrogram

I chose a motto for RelayHelper  - “You can just see”. So the spectrogram is the feature that proves one more time that motto. I wanted to have such frequency-time signal representation a long time ago and I can say that now I use it all the time just to satisfy my curiosity about what’s happening under the hood during short circuits and other events.

There are two ways to enable Spectrogram on the analog channel.

1 Switch the main window of the Comtrade page to the extended view.

Article content

Click on the Spectrogram button in the measurement section

Article content

2 In the Calculations menu select Spectorgram->Channel->(select analog channel from the list).

Article content

Spectrogram activated on 750 kV transmission line phase C voltage channel during single phase AR with default settings (Window size -  2 cycles, Noise threshold - 2%, Amplitude gain -  1).

Article content

Note that frequency scale is shown left to the measurement section. Frequency range depends on the file sampling frequency. High harmonics are usually very small so the spectrogram values are averaged using the RMS method across frequency bins.

Article content

Spectogram settings can be changed in the Calculations menu.

Increasing Window size, you increase frequency resolution but decreasing time precision. Frequency Resolution is calculated automatically based on file sampling frequency and window size. Noise threshold – removes all data below selected value (in percent of maximum value). Using Amplitude gain you can increase the brightness of visualization. 

The same phase C voltage channel with Window size -  4 cycles, and  Noise threshold - 0%.

Article content

The same with Amplitude gain -  4.

Article content

Now the third harmonic content can be seen after the CB phase was closed.

Close up look at the moment when the secondary arc extinguished.

Article content

Transformer inrush current. Window size -  4 cycles, Noise threshold - 0%, Amplitude gain -  1.

Article content

1GW generator neutral voltage during single phase short circuit in the 330 kV grid. 9 harmonic (450 Hz) can be noted. Window size -  4 cycles, Noise threshold - 0%, Amplitude gain -  1.

Article content

Spectrogram calculation requires a lot of power, so it can be enabled on one channel. Also there can be problems with files with high sampling frequency and big Window size settings.

I’ll be happy to see your thoughts. Have you tried it already?

RelayHelper



To view or add a comment, sign in

More articles by Andriy Mukhamet

  • Complex numbers calculator in RelayHelper

    We are currently working on a minor RelayHelper release, which will include new protection modules, bug fixes, and…

    4 Comments
  • Session saving in RelayHelper (Pro users)

    It’s already too ordinary to talk about my favorite RelayHelper features but they really are. One of my…

    1 Comment
  • CEV file support in RelayHelper

    You know, I love SEL products, and even more people from the company with which I’ve already communicated. Syncrowave…

    2 Comments
  • RelayHelper and Cloud Storages

    Another RelayHelper feature I can’t imagine my workflow without is the cloud storage. I just upload or save event file…

  • Power protection modules in RelayHelper 3

    One more type of features that appeared in the new version. Let’s look at how you can use them.

  • Trajectory drawing in RelayHelper

    This is my favorite feature in the new version. Let me remind you that in RelayHelper 3 all protection calculators have…

    7 Comments
  • Fault location calculation in RelayHelper app

    I’ve just finished reading Harry Potter and something feels unrealistic. After all those bright flashes and loud bangs,…

    4 Comments
  • RelayHelper Spectrogram 2. How to measure spotted harmonics.

    It’s very obvious to me because I’m used to the app, but after my last post I realized it might not be obvious to other…

  • Protection systems maloperation statistics

    Before I start, I would like to note that, in my opinion, protection personnel often tend to shift the real causes of…

    5 Comments
  • 7SA522 malfunction case

    Some time ago we had one interesting case of the Siemens 7SA522 malfunction. We made our own investigation and also…

    28 Comments

Others also viewed

Explore content categories